ABB
1SAZ321201R2002TA75DU-32M
TA75DU-32M
Thermal overload protection relay (TOR) - ABB (TA75DU series) - TA75DU-32M - rated current 22A...32A (adjustable) - 15kW (400/415Vac) - Direct mounting on cont. (54mm width) - 1NO+1NC aux. contacts - direct connection to contact. (ingoing)
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
Brand
SKU
1SAZ321201R2002
Online Price
RM 452.00
Discount
50.0%
Net Price
RM 226.00
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
ABB - TA75DU series thermal overload relays1SAZ321201R2002
Description
Thermal overload protection relay (TOR) - ABB (TA75DU series) - TA75DU-32M - rated current 22A...32A (adjustable) - 15kW (400/415Vac) - Direct mounting on cont. (54mm width) - 1NO+1NC aux. contacts - direct connection to contact. (ingoing)
Specifications
Primary brand
ABB
Main function
Thermal Overload Relay (TOR)
Product series / family name
TA75DU series
Network frequency
DC or 50/60 Hz
Functions
Thermal overload protection relay (TOR)
Manual / automatic reset function
Test trip function
Stop function
Rotary knob for adjusting rated motor current
Manual / automatic reset function
Test trip function
Stop function
Rotary knob for adjusting rated motor current
Design
bimetallic tripping elements
Poles
3-poles (3P)
Rated current
22A...32A (adjustable)
Rated active power (kW)
15kW (400/415Vac)
Rated operating voltage (Ue)
(IEC) 690 V
(UL/CSA) 600 V
(UL/CSA) 600 V
Rated impulse voltage (Uimp)
6 kV
Rated insulation voltage (Ui)
690 V
Connection type
direct connection to contact. (ingoing)
Screw-clamp connections (outgoing)
Screw-clamp connections (outgoing)
Protection functions
3-phase overload
Phase loss
Thermal overload Class 10A
Phase loss
Thermal overload Class 10A
Protection settings
Thermal protection (Overload) -- 22A...32A (adjustable)
Net Height (mm)
90 mm
Net Width (mm)
54 mm
Net Depth (mm)
111 mm
Mounting mode
Direct mounting on cont.
Contacts type
1NO+1NC aux. contacts
Ambient air temperature for operation
-25...+55 °C
Visual position indicator
Trip indication on the front
Technical compatibility with
Suitable for 3-phase applications and DC applications
AX50-AX80 series contactors
AX50-AX80 series contactors
Customs Tariff Number
85364900
Minimum current
22 A
Maximum current
32 A
Power dissipation/losses
at rated operating conditions per pole 1.4W...3 W
Order code / Manufacturer SKU
TA75DU-32M
Manufacturer product status
Commercialized
EAN code
4013614482632
Compliant with standard(s)
IEC /EN60947-4-1
IEC /EN60947-1
UL508
CSA22.2 No.14
IEC /EN60947-1
UL508
CSA22.2 No.14
Class
10A
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - Thermal Overload Relays - Tripping Class 20 - datasheet.pdf | 22 Aug 2022 | English (US) |