Schneider Electric
A9F74340Acti9 iC60N 3P 40A C curve 10kA
Acti9 iC60N 3P 40A C curve 10kA
Miniature Circuit Breaker (MCB) - Schneider Electric (Acti9 iC60N) - Rated current 40A - 3 poles (3P) - C-curve - Short circuit breaking capacity (Icu) 10kA (415Vac) - 3 modules - Cage-clamp - DIN rail mounting
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
Brand
SKU
A9F74340
Online Price
RM 353.00
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
Click on the colored tile to view a product selector for this product series:
A9F74340Schneider Electric - Acti9 iC60N
Description
Miniature Circuit Breaker (MCB) - Schneider Electric (Acti9 iC60N) - Rated current 40A - 3 poles (3P) - C-curve - Short circuit breaking capacity (Icu) 10kA (415Vac) - 3 modules - Cage-clamp - DIN rail mounting
Specifications
Primary brand
Schneider Electric
Secondary brand
Merlin Gerin
Main function
Miniature Circuit Breaker (MCB)
Product series / family name
Acti9
Sub-range name
iC60N
Functions
Miniature Circuit Breaker (MCB)
Rated current
40A
Rated Voltage (AC) - Phase-to-neutral
240 V
Rated operating voltage (Ue)
440 V
Rated Voltage (DC)
12-180Vdc
Rated impulse voltage (Uimp)
6 kV
Rated insulation voltage (Ui)
500 V
Poles
3 Pole(s)
Protected poles
3 Pole(s)
Tripping curve
C
Ultimate short circuit current breaking capacity (Icu)
36kA (130Vac)
20kA (240Vac)
10kA (415Vac)
6kA (440Vac)
10kA (180Vdc; 3 poles in series)
20kA (240Vac)
10kA (415Vac)
6kA (440Vac)
10kA (180Vdc; 3 poles in series)
Short circuit current breaking capacity (Icn)
6 kA
Service short circuit current breaking capacity (Ics)
27kA (133Vac)
15kA (240Vac)
7.5kA (415Vac)
4.5kA (440Vac)
10kA (180Vdc; 3 poles in series)
15kA (240Vac)
7.5kA (415Vac)
4.5kA (440Vac)
10kA (180Vdc; 3 poles in series)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(AC) 75 %
(DC) 100 %
(DC) 100 %
Size in modules (1 module = 18mm)
3 Module(s)
Mounting mode
DIN rail
Net Height (mm)
91 mm
Net Width (mm)
54 mm
Net Depth (mm)
78.5 mm
Technology used in component
Visitrip (visible mechanical trip indication)
VisiSafe (positive breaker poles open indication)
VisiSafe (positive breaker poles open indication)
Electrical durability (with load)
10 000 operations
Mechanical durability (at no load)
20 000 operations
Manufacturer product status
Commercialized
Rated Voltage (AC) - Phase-to-phase
440 V
Compliant with standard(s)
IEC 60898-1
IEC 60947-2
IEC 60947-2
Degree of pollution
3
Type of terminals