Schneider Electric
EZC100N4063EZC100N 4P 63A
EZC100N 4P 63A
Molded/Moulded Case Circuit Breaker (MCCB) - Schneider Electric / Merlin Gerin (EasyPact EZC) - EZC100N 4P 63A - 4 poles (4P3d) - Rated current 63A - Rated voltage 250Vdc - Short circuit breaking capacity (Icu) 15kA (400-415Vac) - Thermal-Magnetic (fixed) trip unit (TMD) - Lug connection
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
EZC100N4063
Online Price
RM 757.50
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Click on the colored tile to view a product selector for this product series:
EZC100N4063Schneider Electric - EasyPact EZC - EZC100N
Description
Molded/Moulded Case Circuit Breaker (MCCB) - Schneider Electric / Merlin Gerin (EasyPact EZC) - EZC100N 4P 63A - 4 poles (4P3d) - Rated current 63A - Rated voltage 250Vdc - Short circuit breaking capacity (Icu) 15kA (400-415Vac) - Thermal-Magnetic (fixed) trip unit (TMD) - Lug connection
Specifications
Primary brand
Schneider Electric
Secondary brand
Merlin Gerin
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
EasyPact EZC
Sub-range name
EZC100N
Functions
Molded/Moulded Case Circuit Breaker (MCCB)
Rated current
63A
Trip current rating
63 AT
Frame current rating
100 AF
Rated impulse voltage (Uimp)
6 kV
Rated insulation voltage (Ui)
690 V
Connection type
Lug
Poles
4 Pole(s)
Protected poles
3 Pole(s)
Ultimate short circuit current breaking capacity (Icu)
25kA (110-130Vac)
25kA (220-240Vac)
18kA (380Vac)
15kA (400-415Vac)
10kA (440Vac)
5kA (550Vac)
5kA (125Vdc)
5kA (250Vdc)
25kA (220-240Vac)
18kA (380Vac)
15kA (400-415Vac)
10kA (440Vac)
5kA (550Vac)
5kA (125Vdc)
5kA (250Vdc)
Service short circuit current breaking capacity (Ics)
5kA (125Vdc)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(380-415Vac) 75 %
Trip unit type
TMD
Thermal-Magnetic (fixed)
Thermal-Magnetic (fixed)
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Electrical durability (with load)
(415Vac; In) 1500 operations
Mechanical durability (at no load)
8500 operations
Rated Voltage (DC)
250 V
Utilisation category
A
Manufacturer product status
Commercialized
Rated Voltage (AC) - Phase-to-phase
550 V
Compliant with standard(s)
IEC60947-2
JIS C8201-2-1
JIS C8201-2-1
Mounting mode
Surface mounting
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
Schneider Electric - Easypact EZC - Catalogue.pdf | 20 Mar 2019 | English (US) |