Schneider Electric
LV429847NSX100N TMD 16A 3P3d
NSX100N TMD 16A 3P3d
Molded/Moulded Case Circuit Breaker (MCCB) - Schneider Electric / Merlin Gerin (Compact NSX) - NSX100N TMD 16A 3P3d - 3 poles (3P3d) - Rated current 16A - Short circuit breaking capacity (Icu) 50kA (380-415Vac) - Thermal-Magnetic (adjustable) trip unit (TMD) - Lug connection
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
Brand
SKU
LV429847
Online Price
RM 1,252.50
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
Click on the colored tile to view a product selector for this product series:
Description
Molded/Moulded Case Circuit Breaker (MCCB) - Schneider Electric / Merlin Gerin (Compact NSX) - NSX100N TMD 16A 3P3d - 3 poles (3P3d) - Rated current 16A - Short circuit breaking capacity (Icu) 50kA (380-415Vac) - Thermal-Magnetic (adjustable) trip unit (TMD) - Lug connection
Specifications
Primary brand
Schneider Electric
Secondary brand
Merlin Gerin
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Compact NSX
Sub-range name
NSX100N
Functions
Molded/Moulded Case Circuit Breaker (MCCB)
Rated current
16A
Trip current rating
16 AT
Frame current rating
100 AF
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
800 V
Connection type
Lug
Poles
3 Pole(s)
Protected poles
3 Pole(s)
Ultimate short circuit current breaking capacity (Icu)
90kA (220-240Vac)
50kA (380-415Vac)
50kA (440Vac)
36kA (500Vac)
35kA (525Vac)
10kA (660-690Vac)
50kA (380-415Vac)
50kA (440Vac)
36kA (500Vac)
35kA (525Vac)
10kA (660-690Vac)
Service short circuit current breaking capacity (Ics)
90kA (220-240Vac)
50kA (380-415Vac)
50kA (440Vac)
36kA (500Vac)
35kA (525Vac)
10kA (660-690Vac)
50kA (380-415Vac)
50kA (440Vac)
36kA (500Vac)
35kA (525Vac)
10kA (660-690Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
100 %
Trip unit type
TMD
Interchangeable
Thermal-Magnetic (adjustable)
Interchangeable
Thermal-Magnetic (adjustable)
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
(Over-current) adjustable from 0.7 - 1.0 x In
(Short-circuit pickup current) fixed at 190A
(Short-circuit pickup current) fixed at 190A
Electrical durability (with load)
(440Vac; In/2) 50000 operations
(440Vac; In) 30000 operations
(440Vac; In) 30000 operations
Mechanical durability (at no load)
50 000 operations
Utilisation category
A
Manufacturer product status
Commercialized
Rated Voltage (AC) - Phase-to-phase
690 V
Compliant with standard(s)
IEC60947-2
NEMA AB1
NEMA AB1
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
MCCB (Moulded Case Circuit Breaker) for advanced applications - 100 to 630A - Compact NSX - Catalogue.pdf | 20 Mar 2019 | English (US) |
Schneider Electric - ComPacT NSX and NSXm - Catalogue.pdf | 31 Oct 2023 | English (US) |