Schneider Electric
LV510485CVS100N TMD 63A 4P3d
CVS100N TMD 63A 4P3d
Molded/Moulded Case Circuit Breaker (MCCB) - Schneider Electric / Merlin Gerin (EasyPact CVS) - CVS100N TMD 63A 4P3d - 4 poles (4P3d) - Rated current 63A - Short circuit breaking capacity (Icu) 50kA (380-415Vac) - Thermal-Magnetic (adjustable) trip unit (TMD) - Lug connection
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
Brand
SKU
LV510485
Online Price
RM 1,636.50
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
Click on the colored tile to view a product selector for this product series:
Description
Molded/Moulded Case Circuit Breaker (MCCB) - Schneider Electric / Merlin Gerin (EasyPact CVS) - CVS100N TMD 63A 4P3d - 4 poles (4P3d) - Rated current 63A - Short circuit breaking capacity (Icu) 50kA (380-415Vac) - Thermal-Magnetic (adjustable) trip unit (TMD) - Lug connection
Specifications
Primary brand
Schneider Electric
Secondary brand
Merlin Gerin
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
EasyPact CVS
Sub-range name
CVS100N
Functions
Molded/Moulded Case Circuit Breaker (MCCB)
Rated current
63A
Trip current rating
63 AT
Frame current rating
100 AF
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
690 V
Connection type
Lug
Poles
4 Pole(s)
Protected poles
3 Pole(s)
Ultimate short circuit current breaking capacity (Icu)
80kA (220-240Vac)
50kA (380-415Vac)
40kA (440Vac)
50kA (380-415Vac)
40kA (440Vac)
Service short circuit current breaking capacity (Ics)
80kA (220-240Vac)
50kA (380-415Vac)
30kA (440Vac)
50kA (380-415Vac)
30kA (440Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
(380-415Vac) 100 %
Trip unit type
TMD
Thermal-Magnetic (adjustable)
Thermal-Magnetic (adjustable)
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
(Over-current) adjustable from 0.7 - 1.0 x In
(Short-circuit) fixed at 500A
(Short-circuit) fixed at 500A
Electrical durability (with load)
(415Vac; In/2) 30000 operations
(415Vac; In) 12000 operations
(415Vac; In) 12000 operations
Mechanical durability (at no load)
30 000 operations
Utilisation category
A
Manufacturer product status
Commercialized
Rated Voltage (AC) - Phase-to-phase
440 V
Compliant with standard(s)
IEC60947-2
IEC60664-1
IEC60664-1
Degree of pollution
3
Related Documents
Name | Last Update | Language |
---|---|---|
MCCB (Moulded Case Circuit Breaker) for standard applications - 100 to 630A - EasyPact CVS - Catalogue.pdf | 20 Mar 2019 | English (US) |