Schneider Electric
MVS16H3MW2L
Manually-operated Air Circuit Breaker (ACB) - Schneider Electric (Easypact MVS) - Withdrawable / Drawout - 3 poles (3P3d) - Rated currrent 1600A - Electronic (ET2I (LI)) trip unit - Short circuit breaking capacity (Icu) 65kA (220-440Vac)
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
MVS16H3MW2L
Online Price
RM 32,570.00
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Schneider Electric - Easypact MVSMVS16H3MW2L
Description
Manually-operated Air Circuit Breaker (ACB) - Schneider Electric (Easypact MVS) - Withdrawable / Drawout - 3 poles (3P3d) - Rated currrent 1600A - Electronic (ET2I (LI)) trip unit - Short circuit breaking capacity (Icu) 65kA (220-440Vac)
Specifications
Primary brand
Schneider Electric
Main function
Air Circuit Breaker (ACB)
Product series / family name
Easypact MVS
Sub-range name
MVS16H
Network frequency
50/60 Hz
Functions
Manually-operated Air Circuit Breaker (ACB)
ZSI (Zone Selective Interlocking)
ZSI (Zone Selective Interlocking)
Rated current
1600A
Trip current rating
1600 AT
Frame current rating
1600 AF
Rated impulse voltage (Uimp)
12 kV
Rated insulation voltage (Ui)
1000 V
Connection type
Withdrawable / Drawout
Poles
3 Pole(s)
Protected poles
3 Pole(s)
Ultimate short circuit current breaking capacity (Icu)
65kA (220-440Vac)
50kA (690Vac)
50kA (690Vac)
Short circuit withstand current (Icw)
(220-440Vac; 1s) 65 kA
(690Vac; 1s) 50 kA
(440-690Vac; 3s) 36 kA
(690Vac; 1s) 50 kA
(440-690Vac; 3s) 36 kA
Service short circuit current breaking capacity (Ics)
65kA (220-440Vac)
50kA (690Vac)
50kA (690Vac)
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
100 %
Trip unit type
Electronic (ET2I (LI))
Protection functions
(L) Protection against overload
(I) Instantaneous protection against short-circuit
(I) Instantaneous protection against short-circuit
Protection settings
(L - Protection against overload) adjustable from 0.4 - 1 x In; time setting 0.5 - 24s
(S - Protection against overcurrent with time delay) adjustable from 1.5 - 10 x In; time setting 0.1 - 0.4s
(I - Instantaneous protection against overcurrent) adjustable from 1.5 - 10 x In
(G - Protection against earth fault) adjustable from 0.2 - 1 x In; 0.1-0.4s
(S - Protection against overcurrent with time delay) adjustable from 1.5 - 10 x In; time setting 0.1 - 0.4s
(I - Instantaneous protection against overcurrent) adjustable from 1.5 - 10 x In
(G - Protection against earth fault) adjustable from 0.2 - 1 x In; 0.1-0.4s
Operating mode
Manual operation
Protection function codes
(ANSI) 49
(ANSI) 50
(ANSI) 50
Display
Trip indication LED
Mechanical durability (at no load)
20 000 operations
Short circuit making capacity (Icm)
(220-440Vac) 143 kA
(690Vac) 105 kA
(690Vac) 105 kA
Manufacturer product status
Commercialized
Rated Voltage (AC) - Phase-to-phase
690 V
Compliant with standard(s)
IEC60947-2
CCC
GOST
CCS
CCC
GOST
CCS
Net weight
40 kg
Degree of pollution
4
Related Documents
Name | Last Update | Language |
---|---|---|
Schneider Electric - EasyPact MVS - Catalogue.pdf | 11 Mar 2019 | English (US) |