Schneider Electric
NW63H13D2EVS
Air Circuit Breaker (ACB) (Withdrawable / Drawout) - Schneider Electric (Masterpact NW / NW63H1) - 3 poles (3P3d) - Rated current 6300A - 6300AF / 6300AT - Electronic trip unit (Micrologic 2.0E (LI); with LCD display (7-segment; 4 digits)) - Short circuit breaking capacity (415Vac) 100kA - Vertical rear connection - including 1 x 200-250Vac/dc opening trip coil / release + 1 door escutcheon
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
NW63H13D2EVS
Online Price
RM 252,600.00
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Click on the colored tile to view a product selector for this product series:
Description
Air Circuit Breaker (ACB) (Withdrawable / Drawout) - Schneider Electric (Masterpact NW / NW63H1) - 3 poles (3P3d) - Rated current 6300A - 6300AF / 6300AT - Electronic trip unit (Micrologic 2.0E (LI); with LCD display (7-segment; 4 digits)) - Short circuit breaking capacity (415Vac) 100kA - Vertical rear connection - including 1 x 200-250Vac/dc opening trip coil / release + 1 door escutcheon
Specifications
Primary brand
Schneider Electric
Secondary brand
Merlin Gerin
Main function
Air Circuit Breaker (ACB)
Product series / family name
Masterpact NW
Sub-range name
NW63H1
Functions
Thermal memory (20 minutes before and after tripping)
Zone Selective Interlocking (ZSI)
Trip history memory (10 last trips)
Zone Selective Interlocking (ZSI)
Trip history memory (10 last trips)
Rated insulation voltage (Ui)
1000 V
Poles
3 Pole(s)
Protected poles
3 Pole(s)
Short circuit withstand current (Icw)
(1s) 100 kA
(3s) 100 kA
(3s) 100 kA
Service short circuit current breaking capacity as a percentage of Icu (Ics%)
100 %
Trip unit type
Micrologic 2.0E (LI)
Electronic
Electronic
Protection settings
(L - Protection against overload) adjustable from 0.4 - 1 x In; time setting 0.5 - 24s
(I - Instantaneous protection against overcurrent) adjustable from 1.5 - 10 x In
(I - Instantaneous protection against overcurrent) adjustable from 1.5 - 10 x In
Measurement accuracy
(Currents) 1.5%
(Voltages) 0.5%
(Power; energy) 2%
(Voltages) 0.5%
(Power; energy) 2%
Protection function codes
(ANSI) 49
(ANSI) 50
(ANSI) 50
Display type
LCD display (7-segment; 4 digits)
LEDs (overload; short circuit; internal fault)
LEDs (overload; short circuit; internal fault)
Electrical durability (with load)
6000 operations
Mechanical durability (at no load)
10 000 operations
Rated current
6300 A
Ultimate short circuit current breaking capacity (Icu)
(220Vac) 100 kA
(415Vac) 100 kA
(440Vac) 100 kA
(525Vac) 100 kA
(690Vac) 100 kA
(415Vac) 100 kA
(440Vac) 100 kA
(525Vac) 100 kA
(690Vac) 100 kA
Service short circuit current breaking capacity (Ics)
(220Vac) 100 kA
(415Vac) 100 kA
(440Vac) 100 kA
(525Vac) 100 kA
(690Vac) 100 kA
(415Vac) 100 kA
(440Vac) 100 kA
(525Vac) 100 kA
(690Vac) 100 kA
Short circuit making capacity (Icm)
(220Vac) 220 kA
(415Vac) 220 kA
(440Vac) 220 kA
(525Vac) 220 kA
(690Vac) 220 kA
(415Vac) 220 kA
(440Vac) 220 kA
(525Vac) 220 kA
(690Vac) 220 kA
Manufacturer product status
Commercialized
Rated Voltage (AC) - Phase-to-phase
690 V
Compliant with standard(s)
IEC60947-2
IEC60664-1
IEC60664-1
Connection type
Withdrawable / Drawout
Vertical rear connection
Vertical rear connection
Net weight
225 kg
Degree of pollution
4
Protection functions
(L) Protection against overload
(I) Instantaneous protection against short-circuit
(I) Instantaneous protection against short-circuit
Measurement function
Currents (RMS) L1; L2; L3
Phase-phase voltage (RMS)
Phase-neutral voltage (RMS)
Active power
Reactive power
Apparent power
Power demand
Power factor
Active energy
Reactive energy
Apparent energy
Phase-phase voltage (RMS)
Phase-neutral voltage (RMS)
Active power
Reactive power
Apparent power
Power demand
Power factor
Active energy
Reactive energy
Apparent energy
Operating mode
Main protection settings by rotary trimmers
Related Documents
Name | Last Update | Language |
---|---|---|
Schneider Electric - Masterpact NT/NW - Catalogue | 15 Feb 2017 | English (US) |